ABB PowerValue 11T G2 6kVA / 6000W UPS Online double conversionSeptember 12, 2024
ABB PowerValue 11T G2 6kVA / 6000W UPS Online double conversion
Description UPS PowerValue 11T G2 6 kVA TECH SPECS GENERAL DATA Output rated power 6.000 W Output power factor 1.0 Topology Online double conversion Parallel configuration Yes, up to 3 UPS Inbuilt batteries Yes/Yes/No INPUT Nominal input voltage 208/220/230/240 VAC Input voltage tolerance 100-276 (load dependent) Input current THDi <3% with full resistive load Frequency range 45-55Hz / 54-66Hz (extendable to 40~70HZ at load < 60%) Power factor ≥0.995 OUTPUT Rated output voltage 208/220/230/240 VAC Voltage tolerance ±1% (referred to 230V) Voltage distortion <1% linear load, <5% non linear load Overload capacity (linear load) on inverter 10m: 102-125% load 30s: 126 to 150% load 500 ms: ≥ 150% load Nominal frequency 50 or 60 Hz Crest factor 3:1 (load supported) EFFICIENCY Overall system efficiency Up to 95% In eco-mode Up to 98% ENVIRONMENT Protection rating IP20 Storage temperature UPS: -25°C to 60°C; Batteries: 0°C to 35°C Operating temperature 0°-40°C (up to 50°C at 50% load) Relative humidity 0% to 95% Altitude (above see level) 1000m without derating BATTERIES Type VRLA (valve regulated lead-acid) Inbuilt batteries 16x9Ah(B) Charging current 0-4A adjustable (B) Recharge time (inbuilt batteries) 4h to 90% COMMUNICATIONS User interface LCD display Optional communication cards SNMP; ModBus; AS400; Environmental monitoring sensor probe STANDARDS Safety IEC/EN 62040-1 EMC IEC/EN 62040-2 Performance IEC/EN 62040-3 Manufacturing ISO 9001:2015, ISO 14001:2015, OHSAS 18001 WEIGHT, DIMENSIONS Weight 53/63/13 Kg Dimensions w x h x d 225 x 589x 452 mm